Shelly EM Gen 3
Shelly EM Gen 3 – Dual-Channel Energy Monitor
Monitor your site’s power usage in real time with the Shelly EM Gen 3. Designed for commercial and industrial use, it measures two single-phase circuits at once, helping you track high-draw equipment, reduce energy costs, and improve efficiency.
Features:
- Wi-Fi & Bluetooth connectivity
 - Two current transformer inputs (contactless)
 - Single phase, dual-channel measurement
 - Dry contact switch for contactor control
 - Local data logs (10 days @ 1-minute intervals)
 - Smart schedules & real-time clock
 - MQTT, HTTP, WebSocket, RPC & webhook support
 - Works with leading automation platforms
 
Perfect for workshops, warehouses, and multi-site operations that need accurate, actionable energy insights.

| 
 Physical  | 
|
| 
 Size (HxWxD):  | 
 37x42x16 mm / 1.46x1.65x0.63 inch  | 
| 
 Weight:  | 
 EM Gen3 - 23 g / 0.81 oz CT 50A - 50 g / 1.76 oz  | 
| 
 Screw terminals max torque:  | 
 0.4 Nm / 3.5 lbin  | 
| 
 Conductor cross section:  | 
 0.2 to 2.5 mm² / 24 to 14 AWG (solid, stranded, and bootlace ferrules)  | 
| 
 Conductor stripped length:  | 
 6 to 7 mm / 0.24 to 0.28 in  | 
| 
 Mounting:  | 
 Wall console, Electrical cabinet  | 
| 
 Shell material:  | 
 Plastic  | 
| 
 Shell color:  | 
 White Charcoal gray  | 
| 
 Connectors color:  | 
 Black  | 
| 
 Environmental  | 
|
| 
 Ambient working temperature:  | 
 -20 °C to 40 °C / -5 °F to 105 °F  | 
| 
 Humidity:  | 
 30 % to 70 % RH  | 
| 
 Max. altitude:  | 
 2000 m / 6562 ft  | 
| 
 Electrical  | 
|
| 
 Power supply:  | 
 110 - 240 V~ 50/60 Hz  | 
| 
 Power consumption:  | 
 < 1.2 W  | 
| 
 Neutral not needed:  | 
 Yes or No  | 
| 
 External protection:  | 
 2 A, tripping characteristic B or C,  | 
| 
 Output circuits ratings  | 
|
| 
 Max. switching voltage:  | 
 240 V~  | 
| 
 Max. switching current:  | 
 2 A/240 V~  | 
| 
 Sensors, meters  | 
|
| 
 Voltmeter (AC):  | 
 110-240 V~ 50/60 Hz  | 
| 
 Voltmeter accuracy:  | 
 ±2%  | 
| 
 Ammeter (AC):  | 
 0 - 80A  | 
| 
 Ammeter accuracy:  | 
 ±2 % (2 - 50 A), ±2 % (1 - 2 A), ±5 % (0 - 1 A)  | 
| 
 Compatible current transformers:  | 
 CT 50A (included in the package) CT 80A  | 
| 
 Power and energy meters:  | 
 Active and apparent power Active and apparent energy Power factor Fundamental active and fundamental reactive energy  | 
| 
 Channel-to-channel calibration minimum load:  | 
 500 W  | 
| 
 No load threshold:  | 
 30 VA per channel  | 
| 
 Measurement data storage:  | 
 At least 10 days of 1 min data resolution  | 
| 
 Data export:  | 
 CSV for PQ recorded values JSON format export through RPC  | 
| 
 Internal-temperature sensor:  | 
 Yes  | 
| 
 Radio  | 
|
| 
 Wi-Fi  | 
|
| 
 Protocol:  | 
 802.11 b/g/n  | 
| 
 RF band:  | 
 2412 - 2472 МHz  | 
| 
 Max. RF power:  | 
 < 20 dBm  | 
| 
 Range:  | 
 Up to 30 m / 100 ft indoors and 50 m / 160 ft outdoors  | 
| 
 Bluetooth  | 
|
| 
 Protocol:  | 
 4.2  | 
| 
 RF band:  | 
 2402 - 2480 MHz  | 
| 
 Max. RF power:  | 
 < 4 dBm  | 
| 
 Range:  | 
 Up to 10 m / 33 ft indoors and 30 m / 100 ft outdoors  | 
| 
 Microcontroller unit  | 
|
| 
 CPU:  | 
 ESP-Shelly-C38F  | 
| 
 Flash:  | 
 8 MB  | 
| 
 Firmware capabilities  | 
|
| 
 Schedules:  | 
 Yes  | 
| 
 Webhooks (URL actions):  | 
 20 with 5 URLs per hook  | 
| 
 Scripting:  | 
 Yes  | 
| 
 MQTT:  | 
 Yes  | 
| 
 Encryption:  | 
 Yes (Transport level)  | 
| 
 Authentication:  | 
 Yes (Application and transport level)  | 
Important: All electrical installation work must be performed by a qualified and licensed electrician. Failure to comply may void product warranties and breach electrical safety laws.